Suivi Activite Telesurveillance 43262142


Infos Telalarme
N° Transmetteur 43262142
N° Equipement 43262142
Voie
N° de ligne telephonique 882397105800561
Equipements sur la meme ligne Telephonique 43262142,
Modele et profil TS KCE - DEFAULT KONE 3G
Statut TS OK
Controle des appels cycliques automatiques Actif
Date de creation CCC
Date dernier appel recu au CCC 10/03/2026 00:10:54
Derniere consigne KC3
du au
Nombre d'appels recus sur les 3 derniers mois 426
Option contrat "Lien vocal" Inclus service et com mobile
 24/7 CLOUDVIEW
Pour acceder au detail des evenements recus, cliquer ici
Type Evenement Type alarme Nbre evenements recus sur les 3 derniers mois Date dernier evenement recu
1006 Elevator Failure TTS line failure 138 02/01/2026 18:18:56
SYSRCA Réception Appel Cyclique 101 10/03/2026 01:10:38
1000 Elevator Failure Serial communication broken on board (both TTS channels) 66 17/02/2026 12:38:37
1109 Elevator Failure Landing door not opened after top of car inspection 65 16/02/2026 16:11:42
1029 Elevator Failure Safety circuit: Pit safety contact open (H1) 47 16/02/2026 13:34:38
1214 Elevator Failure Jumper failure on KCECCG KCEAPS connector 39 02/01/2026 12:05:16
4015 Elevator Failure Alarm button is stuck 37 28/01/2026 06:25:34
1607 Elevator Failure Reopen device active too long 20 26/02/2026 09:41:18
1003 Elevator Failure Serial communication broken on board (TTS-2) 14 17/02/2026 11:52:52
1002 Elevator Failure Serial communication broken on board (TTS-1) 10 17/02/2026 11:52:53
1068 Elevator Failure 24V power supply voltage out of +- 20 % range 9 30/01/2026 10:14:06
4016 Elevator Failure KCEAPM 24V power failed (mains missing) 9 13/02/2026 13:52:03
1099 Elevator Failure Main stop switch open 8 30/01/2026 10:14:05
1799 Elevator Failure Self check mode stuck. 6 28/01/2026 12:07:00
1840 Elevator Failure KCEMSC missing from TTS-2 6 28/01/2026 12:07:00
1114 Elevator Failure Pit inspection mode input failure 5 13/02/2026 11:41:03
1839 Elevator Failure KCEMSC missing from TTS-1 5 28/01/2026 12:07:00
1004 Elevator Failure TTS serial communication broken. One channel 4 28/01/2026 12:07:09
1031 Elevator Failure Safety circuit: Landing door opened during drive 4 17/02/2026 14:01:23
1062 Elevator Failure KCEMSC board failure - No reciprocal communication 4 28/01/2026 12:06:57
1161 Elevator Failure KCEDZS board failure - Self check failed 4 02/01/2026 09:09:38
1167 Elevator Failure Board changed after setup 4 17/02/2026 12:39:46
1175 Elevator Failure Safety system in Safe mode 4 28/01/2026 12:06:57
200 System failure: KCE System failure: KCE 4 12/12/2025 11:39:49
2000 Elevator Failure Missing COP 4 17/02/2026 11:53:01
4018 Elevator Failure KCEAPM has no connection to KCECPU 4 08/02/2026 17:01:49
1011 Elevator Failure Car door contact opened during drive (C5) 3 17/02/2026 13:58:04
1039 Elevator Failure Door open monitoring functioned 3 13/02/2026 12:47:31
1182 Elevator Failure KCEMSC configuration failure - DIP position changed 3 13/02/2026 12:47:31
2342 Elevator Failure KCEDZS board failure - Reciprocal communication 3 02/01/2026 09:10:43
2355 Elevator Failure KCEDZS board failure - variant detection 3 02/01/2026 09:09:39
2384 Elevator Failure KCEDZS board failure - Test input 3 02/01/2026 09:10:37
4017 Elevator Failure KCEAPM 12V power failed (battery failure) 3 17/02/2026 12:52:52
1030 Elevator Failure Safety circuit: buffer contact or OSG contact (H2) 2 28/01/2026 13:42:40
1035 Elevator Failure Unintended movement 2 28/01/2026 12:06:57
1054 Elevator Failure Safety circuit: ground fault 2 28/01/2026 13:42:40
1188 Elevator Failure Safety circuit: Buffers up input (H7) 2 13/02/2026 12:47:31
2340 Elevator Failure KCEDZS board failure - 5 V power supply 2 02/01/2026 09:09:51
2341 Elevator Failure KCEDZS board failure - 3.3 V power supply 2 02/01/2026 09:09:49
2349 Elevator Failure KCEDZS Setup data lost 2 17/02/2026 12:39:40
1033 Elevator Failure safety circuit: Buffers supervision. Up input failure 1 13/02/2026 12:39:52
2339 Elevator Failure KCEDZS 24 V power supply failure 1 02/01/2026 09:11:52