Suivi Activite Telesurveillance 43780926


Infos Telalarme
N° Transmetteur 43780926
N° Equipement 43780926
Voie
N° de ligne telephonique 882397120939775
Equipements sur la meme ligne Telephonique 43780926,
Modele et profil TS KCE - DEFAULT KONE 3G
Statut TS OK
Controle des appels cycliques automatiques Actif
Date de creation CCC
Date dernier appel recu au CCC 09/03/2026 21:50:12
Derniere consigne KC3
du au
Nombre d'appels recus sur les 3 derniers mois 342
Option contrat "Lien vocal" Inclus service et com mobile
 24/7 CLOUDVIEW
Pour acceder au detail des evenements recus, cliquer ici
Type Evenement Type alarme Nbre evenements recus sur les 3 derniers mois Date dernier evenement recu
1702 Elevator Failure Start timeout 174 13/01/2026 18:13:15
1703 Elevator Failure Start failed 108 28/12/2025 09:45:27
SYSRCA Réception Appel Cyclique 98 09/03/2026 22:50:06
1094 Elevator Failure Induced noise in landing door contact 66 14/01/2026 20:15:40
1607 Elevator Failure Reopen device active too long 20 16/02/2026 13:38:28
1015 Elevator Failure Safety circuit: car top balustrade not up while on top of car inspection mode (C8) 19 05/03/2026 11:58:53
1039 Elevator Failure Door open monitoring functioned 18 06/03/2026 15:58:25
1140 Elevator Failure Safety circuit: Inspection up limit 15 05/03/2026 11:58:53
1055 Elevator Failure Safety circuit: power supply voltage out of 10 % range 10 13/01/2026 18:13:11
1115 Elevator Failure KCEMSC board failure - Safety input power supply 8 05/03/2026 02:03:33
1839 Elevator Failure KCEMSC missing from TTS-1 7 06/03/2026 09:36:53
1840 Elevator Failure KCEMSC missing from TTS-2 7 06/03/2026 09:36:53
1053 Elevator Failure KCEMSC board failure - Safety input cross check 6 05/03/2026 17:43:22
1057 Elevator Failure Safety circuit: power supply voltage out of 20 % range 6 05/03/2026 02:03:33
1004 Elevator Failure TTS serial communication broken. One channel 5 05/03/2026 11:58:53
100 Temporary Fault Unclassified Alarm 4 09/03/2026 05:35:49
1188 Elevator Failure Safety circuit: Buffers up input (H7) 4 16/02/2026 10:28:16
1029 Elevator Failure Safety circuit: Pit safety contact open (H1) 2 13/01/2026 16:19:06
1030 Elevator Failure Safety circuit: buffer contact or OSG contact (H2) 2 13/01/2026 16:19:06
1034 Elevator Failure safety circuit: Buffers supervision. Down input failure 2 13/01/2026 16:19:06
1072 Elevator Failure Energy saving failure 2 13/01/2026 16:19:05
1175 Elevator Failure Safety system in Safe mode 2 06/03/2026 03:43:32
102 Temporary Fault Test Alarm 1 29/12/2025 10:16:18
1062 Elevator Failure KCEMSC board failure - No reciprocal communication 1 06/03/2026 03:43:32
200 System failure: KCE System failure: KCE 1 05/03/2026 02:06:54
4016 Elevator Failure KCEAPM 24V power failed (mains missing) 1 05/03/2026 00:18:53